博文

目前显示的是标签为“water cooled screw chiller”的博文

The Solution of Food and Beverage Workshop Ice Water System

图片
Ⅰ.Demand Situation Food and beverage workshop ice water system engineering. The ice water system mainly meets the requirements of ice water on the production line. The required ice water temperature has two, one is 5 degrees ice water; the other is -5 degrees. Ⅱ. Load Calculation 1.5 degrees ice water total cooling capacity is 1500KW 2.-5 degrees ice water total cooling capacity 750KW 3.12 degree water tank: 2*15m³stainless steel insulated water tank 4.-5 degree water tank: 2*15m³stainless steel insulated water tank Ⅲ.Design Ideas Due to the different ice water temperatures required by the production line, in order to reduce operating costs, chillers and ice water systems are selected according to different temperatures. Ⅳ.Equipment selection 1.Main Equipment: The 5 degree ice water system selected one H.stars  water-cooled industrial chiller  (model 40STD-2020WDI2, cooling capacity 2016KW, input power 348.4KW), equipped...